Siemens S7-1200 Modbus TCP Communication and Applications Guide

Explore the Siemens S7-1200 PLC’s Modbus TCP communication capabilities, including the MB_CLIENT and MB_SERVER instructions, hardware setup, and practical applications for seamless data transfer.

Introduction: Understanding Siemens S7-1200 Modbus TCP Communication

Siemens S7-1200 PLC supports Modbus TCP communication, enabling it to function either as a Modbus TCP client (master) or as a server (slave). This guide offers a detailed explanation of the Modbus TCP communication instructions used in the Siemens S7-1200 PLC, covering both theoretical and practical aspects to ensure efficient data transmission between devices.

1. Modbus TCP Communication Instructions

Siemens S7-1200 PLC primarily uses two key instructions to facilitate Modbus TCP communication:

1.1. MB_CLIENT Instruction: Setting Up the Client Connection

The MB_CLIENT instruction is used in the client (master) PLC to establish a connection to a Modbus TCP server. It sends requests and receives responses over a TCP/IP network. This instruction requires several parameters, including:

  • Connection Parameters: Defines the server’s IP address and port number.
  • Request Parameters: Specifies the function code, data address, and data length for the communication.
  • Response Handling Parameters: Used to manage the reception of data after the request.

1.2. MB_SERVER Instruction: Listening for Client Requests

The MB_SERVER instruction is used in the server (slave) PLC to listen for requests from a Modbus client. It processes incoming requests and returns the appropriate responses. The necessary parameters for the MB_SERVER instruction include:

  • Connection Parameters: Setup for the PLC to listen on a specific port.
  • Request Handling Parameters: Used to manage and process incoming requests.
  • Response Parameters: Defines how to send data back to the client.

2. Modbus TCP Communication Applications

Implementing Modbus TCP communication in real-world applications involves several steps, including hardware setup, programming, and configuration. Below are key considerations for setting up and using Modbus TCP in Siemens S7-1200 PLCs.

2.1. Hardware Setup for Modbus TCP Communication

Before starting the Modbus TCP communication, ensure that the PLC and the Modbus TCP server (or another PLC) are correctly connected via an Ethernet network. The network setup usually involves:

  • Ethernet Cables: Properly connect the PLCs to the network.
  • Network Devices: Configuring switches, routers, or hubs to ensure proper data flow.

2.2. IP Address and Port Configuration

For successful communication, both the client and server PLCs need to be assigned unique IP addresses and port numbers. In the Siemens TIA Portal, configure these settings for each PLC in the device configuration section. The client PLC must know the server’s IP address and port number to establish a connection.

2.3. Programming and Configuration

  • Client PLC Programming:
    The MB_CLIENT instruction is programmed in the client PLC. A function block is created where the MB_CLIENT instruction is called, and various parameters are set, such as connection details, request information, and data storage locations for sending and receiving data.
  • Server PLC Programming:
    Similarly, the MB_SERVER instruction is used in the server PLC. A function block is created to call the MB_SERVER instruction and handle incoming requests. The server PLC also requires a data block to store the data that will be sent to the client.
  • HMI Configuration:
    If a touchscreen or HMI device is used, ensure it is configured to interact with the PLC variables, displaying and inputting data in real time. This is critical for monitoring and controlling the process directly from the HMI.

2.4. Communication Testing

Once programming is complete, it’s important to test the communication between the client and server PLCs. Perform the following:

  • Data Testing: On the client HMI, enter data to send to the server and verify if the data appears correctly on the server HMI.
  • Error Diagnosis: If the data transfer doesn’t work, check the IP addresses, ports, and cable connections for issues.

3. Important Considerations for Modbus TCP Communication

3.1. Modbus TCP Instruction Versions

Different versions of TIA Portal or STEP 7 might have variations in the implementation of Modbus TCP instructions. Always refer to the specific version’s manual to ensure you’re using the correct syntax and parameters.

3.2. Data Block Configuration

When setting up data blocks for sending and receiving data, be careful about the following:

  • Avoid Optimized Block Access: This setting can interfere with proper data retrieval, so disable optimized block access to ensure seamless communication.

3.3. Error Handling in Communication

While working with Modbus TCP, various errors can arise, such as:

  • Connection Failures: Issues with network connectivity.
  • Data Errors: Corrupt or incorrect data transmission.
  • Timeouts: Delays that occur during the communication process.

To mitigate these issues, implement error handling logic in your programming to manage unexpected events.

3.4. Network Security

Since Modbus TCP operates over an Ethernet network, network security is a crucial consideration. You should:

  • Use firewalls to protect the communication network.
  • Implement VPNs for secure remote access.
  • Regularly monitor network traffic for suspicious activity.

4. Conclusion

Siemens S7-1200 PLC’s Modbus TCP communication capabilities offer a reliable and efficient way to connect multiple PLCs and devices for data transfer in industrial automation systems. By understanding and applying the MB_CLIENT and MB_SERVER instructions, configuring IP addresses and ports, and following best practices for programming and hardware setup, engineers can optimize their systems for seamless operation. Always consider the network security and error handling strategies to ensure robust communication.